Seismic behavior of electrical cabinets with cast-in-place anchors: influence of concrete cracks and multi-bay installation
- 문서 유형
- 연구출판물 · 학술지 논문
- 등재
- KCISCIEScopus
- 저널 순위
- JCR Q1Scopus Q1KCI Q3
- 저널
- NUCLEAR ENGINEERING AND TECHNOLOGY58(5) · 2026
- 피인용
- Web of Science 1Scopus 1KCI 0
- FWCI (Scopus)
- 0
- JCR IF
- JCR 2024 2.6
- ISSN
- 1738-5733
저자
- 전법규제1저자Pusan Natl Univ, Seism Res & Test Ctr, 49 Busandaehak Ro, Yangsan 50612, Gyeongnam, South Korea
- 김성완교신저자Pusan Natl Univ, Seism Res & Test Ctr, 49 Busandaehak Ro, Yangsan 50612, Gyeongnam, South Korea
- 박동욱Pusan Natl Univ, Seism Res & Test Ctr, 49 Busandaehak Ro, Yangsan 50612, Gyeongnam, South Korea
- 이채빈Pusan Natl Univ, Seism Res & Test Ctr, 49 Busandaehak Ro, Yangsan 50612, Gyeongnam, South Korea
- Hahm, DaeGiKorea Atom Energy Res Inst, Struct & Seism Safety Res Div, 111 Daedeok Daero 989 beon Gil, Daejon 34057, South Korea
- Lee, Hong-Pyo교신저자Korea Hydro & Nucl Power Co LTD, Cent Res Inst, 70 Yuseong Daero 1312 Beon Gil, Daejeon 34101, South Korea
초록
Electrical cabinets are typically assembled in a multi-bay configuration, connecting two or more modules, and the structural implications of this setup must be carefully addressed. Concrete foundation cracks, often observed during field investigations at power plants, represent a common form of support deterioration. This study fabricated concrete foundations to simulate intact conditions and cracked conditions with 0.5 mm and 1.0 mm wide cracks at anchor locations. A simplified electrical cabinet model was constructed in single-bay, two-bay, and three-bay configurations and anchored to the concrete foundations using cast-in-place anchors to consider the effects of multi-bay configuration and support deterioration. Three-axis shaking table tests were conducted, including resonant frequency search and seismic fragility tests. The results indicated that cracks at the anchor locations can increase the uncertainty in the cabinet's resonant frequency. Specifically, when the concrete foundation was intact, seismic performance improved as the number of connected bays increased. However, cracks up to 1.0 mm in width degraded the seismic performance of multi-bay configurations but had a negligible impact on the single-bay cabinet. Moreover, distinct damage modes were observed between single-bay and multi-bay conditions.
키워드
AnchorElectrical cabinetNuclear power plantSeismic fragilitySeismic performanceShaking table test