Limit state assessment of the relative displacement of a vertical pipe system connected with stainless-steel press joints

문서 유형
연구출판물 · 학술지 논문
등재
SCIEScopus
저널 순위
JCR Q1Scopus Q1
저널
JOURNAL OF BUILDING ENGINEERING115 · #114446 · 2025
피인용
Web of Science 0Scopus 0
FWCI (Scopus)
0
JCR IF
JCR 2024 7.4
ISSN
2352-7102

저자

  1. 김성완제1저자Pusan Natl Univ, Seism Res & Test Ctr, 49 Busandaehak Ro, Yangsan 50612, Gyeongnam, South Korea
  2. 전법규Pusan Natl Univ, Seism Res & Test Ctr, 49 Busandaehak Ro, Yangsan 50612, Gyeongnam, South Korea
  3. 박동욱Pusan Natl Univ, Seism Res & Test Ctr, 49 Busandaehak Ro, Yangsan 50612, Gyeongnam, South Korea
  4. 장성진교신저자Pusan Natl Univ, Seism Res & Test Ctr, 49 Busandaehak Ro, Yangsan 50612, Gyeongnam, South Korea

초록

Fire protection piping systems, which are categorized as nonstructural systems, constitute critical infrastructure required to function following seismic events. Maintaining the integrity of fire protection piping systems during natural disasters such as earthquakes remains essential. In piping systems, relative displacement exceeding allowable limits at fittings and joints substantially contributes to seismic losses. Weldless joints are easier to install, maintain, or reinforce than conventional fusion-bonded connections, making them suitable for buildings, fire protection, and water supply piping. As corrosion-resistant tubing gains prevalence, the application of weldless press joints is also increasing. Therefore, the substitutability of seismic separation joints with press joints must be verified. In this study, a two-story steel-frame structure was constructed, and a vertical pipe system assembled using press joints was installed based on the National Fire Protection Association 13 standard. To assess the seismic safety of the vertical pipe system, inplane cyclic loading was applied according to the maximum allowable interstory drift, as specified in the American Society of Civil Engineers 7-16 standard. The seismic performance of components, including fittings and joints that are vulnerable to seismic loads in a vertical pipe system, was evaluated using a rotation-driven regimen. To confirm the margin of safety for the evaluated seismic performance, fixed-magnitude repeated excitation was applied to assess the limit states. The experimental results demonstrated that the vertical pipe system exhibits sufficient seismic performance, and press joints are viable as seismic separation joints.

키워드

Press jointSeismic safetySeismic separation jointVertical pipe systemWeldless jointDIGITAL IMAGE CORRELATIONSEISMIC FRAGILITYNONSTRUCTURAL COMPONENTSPIPING SYSTEMNATURAL-GASEARTHQUAKEPIPELINESPERFORMANCENORTHRIDGEBEHAVIOR