A case study on the failure of the electrical panel of nuclear power plants by shaking table tests
- 문서 유형
- 연구출판물 · 학술지 논문
- 등재
- KCISCIEScopus
- 저널 순위
- JCR Q1Scopus Q1KCI Q3
- 저널
- NUCLEAR ENGINEERING AND TECHNOLOGY57(7) · 2025
- 피인용
- Web of Science 7Scopus 8KCI 0
- FWCI (Scopus)
- 1.33
- JCR IF
- JCR 2024 2.6
- ISSN
- 1738-5733
저자
- 전법규제1저자Pusan Natl Univ, Seism Res & Test Ctr, 49 Busandaehak Ro, Yansan 50612, Gyeongnam, South Korea
- 박동욱Pusan Natl Univ, Seism Res & Test Ctr, 49 Busandaehak Ro, Yansan 50612, Gyeongnam, South Korea
- 김성완교신저자Pusan Natl Univ, Seism Res & Test Ctr, 49 Busandaehak Ro, Yansan 50612, Gyeongnam, South Korea
- 장성진교신저자Pusan Natl Univ, Seism Res & Test Ctr, 49 Busandaehak Ro, Yansan 50612, Gyeongnam, South Korea
- Eem, SeunghyunKyungpook Natl Univ, Dept Convergence & Fus Syst Engn, Major Plant Syst Engn, Sangju, South Korea
- Park, JunheeKorea Atom Energy Res Inst, Struct & Seism Safety Res Div, 111 Daedeok Daero 989 Beon Gil, Daejeon 34057, South Korea
초록
The clearest method to evaluate seismic performance is to test the equipment installed in nuclear power plants using shaking table tests. Accordingly, research is conducted to directly evaluate the seismic performance and limit state via shaking table tests on equipment identical to the specifications supplied to nuclear power plants. Specifically, the fragility level test through the actual equipment test, which primarily aims to investigate the equipment's critical acceleration and failure mode, was carried out. This paper summarizes the limit state of the electrical panel for a nuclear power plant observed via the shaking table test through the damage mode using an actual equipment test. The actual equipment test was performed to check the critical acceleration level and analyze the damage mode on the electrical panels to be tested. Results of the shaking table test on the electrical panel confirmed that functional abnormalities were attributed to shaking and impact. It was also found that functional abnormalities and structural failure can occur in earthquakes of similar magnitude. Moreover, structural failure observed mostly involves damage to the door lock, damage to and/or detachment of the internal parts, and damage to connecting members, usually concentrated in the components that support heavy parts.
키워드
Electrical panelFailure modeNuclear power plantsSeismic performanceShaking table tests
식별자
- Scopus EID
- 2-s2.0-85218128371
- WoS UID
- 001453995100001
- KCI
- ART003202899



로그인
연구물 목록으로