본문 바로가기

Effect of room size, shape, AC placement, and air leakage on indoor airborne viral transmission

문서 유형
연구출판물 · 학술지 논문
등재
SCIEScopus
저널 순위
JCR Q1Scopus Q1
저널
BUILDING AND ENVIRONMENT244 · 2023
피인용
Web of Science 3Scopus 5
FWCI (Scopus)
0.34
JCR IF
JCR 2022 7.4
ISSN
0360-1323

저자

  1. 샤우드리 카일라시제1저자Pusan Natl Univ, Sch Mech Engn, Pusan, South Korea
  2. Krishnaprasad, K. A.Univ Florida, Dept Mech & Aerosp Engn, Gainesville, FL 32611 USA
  3. Zgheib, N.교신저자Univ Texas Rio Grande Valley, Dept Mech Engn, Edinburg, TX 78539 USA
  4. 하만영Pusan Natl Univ, Sch Mech Engn, Pusan, South Korea
  5. Balachandar, S.Univ Florida, Dept Mech & Aerosp Engn, Gainesville, FL 32611 USA

초록

We conducted Euler–Lagrange Reynolds-Averaged Navier–Stokes simulations with statistical overloading to investigate the effect of room shape, air-condition (AC) location, and the presence of an open window on indoor airborne viral transmission, particularly as it relates to the spatio-temporal distribution of viral-laden droplet nuclei. Two room geometries were considered with two different AC types positioned at different locations within each room. We considered the case of perfect filtration where pathogens can exit the room through ventilation, air leakage through an open window, turbulent wall deposition, and by gravitational settling onto the bottom floor. We observe the room-averaged concentration to decay at the rate estimated from the well-mixed model and therefore to be independent of room size and shape or AC type and placement. It is also independent of whether or not there is an open window. However, we find that the departure from well-mixedness, which has been quantified using a time- and source-to-sink separation-dependent correction function γ, is affected by room shape and AC placement. More specifically, indoor spaces where the AC is installed on one end of the room allow droplet nuclei ejected on one end of the room to travel longer distances before being removed from the room as opposed to indoor spaces in which the AC is installed at the center of the room. The present results allow generalization of a simple model for the accurate prediction of viral quanta inhaled by an individual in any indoor environment.

키워드

AC locationCOVID-19Indoor viral transmissionPathogen concentrationRoom shapeEXPOSURE

식별자

Scopus EID
2-s2.0-85171392025
WoS UID
001081808500001