Effects of a thermodynamic non-equilibrium two-phase flow of R-600a at subcooled temperature condition on the performance of a vapor compression refrigeration system

문서 유형
연구출판물 · 학술대회 발표논문
등재
Scopus
저널
Refrigeration Science and Technology2018-June · pp.77 · 2018
피인용
Scopus 0
FWCI (Scopus)
0

저자

  1. 고재덕제1저자School of Mechanical Engineering, Pusan National University, Busan, South Korea
  2. 정지환School of Mechanical Engineering, Pusan National University, Busan, South Korea

초록

Some previous research demonstrated the existence of a thermodynamic non-equilibrium two-phase flow of the refrigerant between the condenser outlet and the expansion device inlet even at thermodynamic subcooled temperature condition where the refrigerant temperature is below the corresponding saturation temperature. In the present study, experiments are carried out to investigate the effects of the thermodynamic non-equilibrium two-phase flow of R-600a at the subcooled condition on the performance of a vapor compression refrigeration system. The enthalpy of the non-equilibrium state refrigerant is calculated using three different methods. Based on the enthalpy values at the outlet of the condenser, the condenser heat rejection rate and the coefficient of performance (COP) of the refrigeration system are evaluated.

키워드

COPNon-equilibrium two-phase flowR-600aVapor compression refrigeration system