중량부품 지지대 보강에 의한 원자력 발전소 배터리 차져의 내진한계상태 비교
Fragility Comparison of Battery Chargers for Nuclear Power Plants depending on Reinforcement of Supporting for Massive Components
- 문서 유형
- 연구출판물 · 학술지 논문
- 등재
- KCI
- 저널 순위
- KCI Q2
- 저널
- 한국소음진동공학회논문집33(3) · pp.264 · 2023
- 피인용
- KCI 1
- ISSN
- 1598-2785
저자
초록
In South Korea, nuclear power plant equipments are designed and qualified according to the Nuclear Regulatory Commission (NRC) Regulatory Guide 1.60 (R.G. 1.60). However, the uniform hazard spectrum (UHS) at the nuclear site in Uljin area exhibits a higher response acceleration in the high frequency range in comparison with R.G. 1.60. In this study, a seismic limit state test considering different response spectra types was executed for battery chargers with and without reinforcement, which is a similar model to that using N.P.P. Battery charger using N.P.P. includes a massive transformer, which is normally fixed to the enclosure with brackets. Brackets should be under high seismic loads because of the transformer mass. Failure modes of the battery charger considered in this study were observed as the structural failure mode in transformer supports (bracket) and functional failure mode in major relay chattering. It seems that the reinforcement for structural failure mode can improve not only structural limit state but also reduce the chattering phenomenon under seismic conditions.
키워드
Battery ChargerElectronic CabinetSeismic AmplificationHigh Frequency MotionShaking Table Test배터리 차져전기 캐비넷지진 증폭고주기진동진동대 실험
식별자
- KCI
- ART002967364



로그인
연구물 목록으로