유사 성능 기기의 지진에 대한 거동특성 분석
Behavioral Characteristics Analysis for Earthquakes of the Similar Performance Equipment
- 문서 유형
- 연구출판물 · 학술지 논문
- 등재
- KCI
- 저널 순위
- KCI Q2
- 저널
- 한국소음진동공학회논문집33(2) · pp.193 · 2023
- 피인용
- KCI 0
- ISSN
- 1598-2785
저자
초록
Damage to nuclear power plants results in loss of life and environmental disasters. Safety-related equipment installed in the nuclear power plants are controlled by electrical control equipment. Safety-related equipment are required to have seismic performance. In this study, the seismic performance of the motor control center (MCC), an electrical control equipment, is tested. Therefore, a shaking table test was conducted using the design response spectrum and uniform hazard spectra. The equipment installed in the nuclear power plants are supplied by various manufacturers. Because the seismic performance of MCC varies depending on the design and manufacturing method, the shaking table test is conducted for two different MCCs with the same function. The dynamic characteristics and shapes of two different types of MCCs were compared, and the seismic performance according to the shape was examined. Additionally, the difference in seismic performance according to the structural shape was examined through seismic fragility tests.
키워드
Electric CabinetMotor Control CenterShaking Table TestSesmic Performance전기캐비닛전동기 제어반진동대 시험내진성능
식별자
- KCI
- ART002951771



로그인
연구물 목록으로