Effects of saturation temperature variation due to pressure drop of working fluid in heat exchanger on heat transfer performance
- 문서 유형
- 연구출판물 · 학술지 논문
- 등재
- KCISCIEScopus
- 저널 순위
- JCR Q3Scopus Q2KCI Q2
- 저널
- JOURNAL OF MECHANICAL SCIENCE AND TECHNOLOGY36(11) · pp.5765 · 2022
- 피인용
- Web of Science 2Scopus 5KCI 1
- FWCI (Scopus)
- 0.14
- JCR IF
- JCR 2021 1.81
- ISSN
- 1738-494X
저자
초록
The effect of the saturation temperature drop on the heat transfer performance of a heat exchanger was analyzed under air-conditioner condensing condition, air-conditioner evaporating condition, and refrigerator evaporating condition. The thermodynamic analysis results show that the heat transfer capacity due to the pressure drop of the saturated refrigerant was at least 2.3 % and at most 91.1 % compared to the evaluated heat transfer capacity assuming no pressure loss. The rate of change of heat transfer capacity was the largest in the order of R600a, R1234yf, R134a, R410A, and R32. Heat exchanger performance simulation under practical air-conditioner operating conditions showed that the heat transfer capacity was reduced by 0.72 % due to refrigerant pressure drop under the condensing condition. On the other hand, the heat transfer capacity was increased by 26.55 % under the evaporating condition.
키워드
Heat exchangerHeat transfer performanceRefrigerantSaturation temperature dropTwo-phase pressure drop2-PHASE FLOW DISTRIBUTIONAIR-SIDE PERFORMANCEGENERAL CORRELATIONPREDICTIVE METHODSREFRIGERANT FLOWMAL-DISTRIBUTIONCONDENSERSYSTEMFRICTIONR600A