Seismic Simulation Test of a Fire Protection Riser Pipe with Fixed Groove Joints
- 문서 유형
- 연구출판물 · 학술대회 발표논문
- 등재
- Scopus
- 저널 순위
- Scopus Q3
- 저널
- IOP Conference Series: Materials Science and Engineering491(1) · 2019
- 피인용
- Scopus 0
- FWCI (Scopus)
- 0
- ISSN
- 1757-8981
저자
- 김성완제1저자교신저자Seismic Research and Test Center, Pusan National University, Mulgeum, Kyungnam Yangsan, South Korea
- 전법규Seismic Research and Test Center, Pusan National University, Mulgeum, Kyungnam Yangsan, South Korea
- Ahn, S. W.Korea Testing Certification, Gunpo, Gyeonggi, South Korea
- Wi, S. W.Korea Testing Certification, Gunpo, Gyeonggi, South Korea
초록
© Published under licence by IOP Publishing Ltd.In this study, seismic simulation tests were conducted on a stainless steel pipe with fixed groove joints for fire protection systems using cyclic loading. When a seismic load occurred, the deformation of the specimen and the response by the relative displacement between the elements were analyzed. To examine the behavior of the tee joints and elbow (vulnerable elements of the specimen) in the range higher than the ±1° minimum deformation angle in the event of an earthquake, the deformation angle was measured using an image processing method. The von Mises stress was also measured at the tee joint and elbow using a 3-axis strain gauge, and the result was compared with the allowable stress criterion to confirm the seismic performance.