Energy performance analysis of textile and capillary tube composite panel system by computational fluid dynamics and real-scale experiments
- 문서 유형
- 연구출판물 · 학술지 논문
- 등재
- SCIEScopus
- 저널 순위
- JCR Q1Scopus Q1
- 저널
- ENERGY AND BUILDINGS258 · 2022
- 피인용
- Web of Science 4Scopus 6
- FWCI (Scopus)
- 0.42
- JCR IF
- JCR 2021 7.201
- ISSN
- 0378-7788
저자
- 배상무제1저자Pusan Natl Univ, Dept Architectural Engn, 2 Busandaehak Ro 63, Busan 46241, South Korea
- 오진환Pusan Natl Univ, Dept Architectural Engn, 2 Busandaehak Ro 63, Busan 46241, South Korea
- Kim, JaeminPohang Technopk, Renewable Energy Convergence Team, 394 Jigok Ro, Pohang 37668, South Korea
- 백은림Pusan Natl Univ, Seism Res & Test Ctr, 49 Busandaehak Ro, Yangsan 50612, South Korea
- 남유진교신저자Pusan Natl Univ, Dept Architectural Engn, 2 Busandaehak Ro 63, Busan 46241, South Korea
초록
© 2021 Elsevier B.V.In South Korea, more than 300,000 buildings are evaluated as remodeling targets. These old buildings consume higher energy per unit area. Moreover, most of them are masonry structures, are vulnerable to earthquakes and can suffer significant damage. Therefore, textile and capillary tube composite panels (TCPs) are used to improve energy and seismic performance of old masonry buildings. In this study, the applicability of TCP to an actual building was confirmed using computational fluid dynamic (CFD). Based on the CFD analysis results, a real-scale experimental plant was constructed. To establish a sustainable method of using TCP, a photovoltaic-thermal (PVT) module that uses solar energy was combined. The applicability of TCPs using the PVT module was reviewed by performing a real-scale experiment. The PVT system could supply hot water at up to 27.6 °C to the TCP in winter. The thermal insulation performance improved with increasing supply water temperature. Especially, in the case of TCP installed indoors, heat could be transferred indoor more effectively than in the case with the TCP installed outdoors.
키워드
Computational fluid dynamicsEnergy performanceHeat storage tankPhotovoltaic-thermalTextile and capillary tube composite panel