15층 철근콘크리트 건물에 설치된 통신설비 면진장치 동적거동에 대한 실험적 연구
An Experimental Study on the Dynamic Behavior of the Seismic Isolator for Telecommunication Equipment Installed in a 15-Story Reinforced Concrete Building
- 문서 유형
- 연구출판물 · 학술지 논문
- 등재
- KCI
- 저널 순위
- KCI Q2
- 저널
- 한국지진공학회논문집 (EESK)25(6) · pp.241 · 2021
- 피인용
- KCI 0
- ISSN
- 1226-525X
저자
초록
Communication facilities play an essential role in disaster situations. Therefore, communication facilities need to have structural and functional safety during and after earthquakes. Recently, technology for partial seismic isolation has been increasing to protect data facilities and communication equipment installed in buildings from earthquakes. However, excessive displacement may occur in the seismic isolator during an earthquake due to the resonance between the building and the seismic isolator having long-period characteristics, which may cause overturning and separation of the installed equipment. In this study, analytical and experimental studies were conducted to evaluate the safety of seismic isolators installed in high-rise buildings. It was confirmed that damages might occur in buildings' seismic isolator, with resonance characteristics of less than 1 Hz.
키워드
Tele-communication equipmentSeismic isolatorLong periodConcrete buildingResonance