본문 바로가기

Dynamic characteristics of single door electrical cabinet under rocking: Source reconciliation of experimental and numerical findings

문서 유형
연구출판물 · 학술지 논문
등재
KCISCIEScopus
저널 순위
JCR Q1Scopus Q2KCI Q3
저널
NUCLEAR ENGINEERING AND TECHNOLOGY53(7) · pp.2387 · 2021
피인용
Web of Science 23Scopus 26KCI 6
FWCI (Scopus)
1.33
JCR IF
JCR 2020 2.341
ISSN
1738-5733

저자

  1. 전법규제1저자KOCED Seismic Simulation Test Center, Pusan National University, 49 Busandaehak-ro, Mulgeum Yangsan Kyungnam 50612 Republic of Korea
  2. Son, Ho-YoungDepartment of Civil Engineering, Kyung Hee University, Yongin-Si, Gyeonggi-Do 17104, Republic of Korea
  3. Eem, Seung-HyunDepartment of Conversion & Fusion System Engineering, Major in Plant System Engineering, Kyungpook National University, Republic of Korea
  4. Choi, In-KilSmart Structural Safety & Prognosis Research Division, Korea Atomic Energy Research Institute, Republic of Korea
  5. Ju, Bu-Seog교신저자Department of Civil Engineering, Kyung Hee University, Yongin-Si, Gyeonggi-Do 17104, Republic of Korea

초록

Seismic qualifications of electrical equipment, such as cabinet systems, have been emerging as the key area of nuclear power plants in Korea since the 2016 Gyeongju earthquake, including the high-frequency domain. In addition, electrical equipment was sensitive to the high-frequency ground motions during the past earthquake. Therefore, this paper presents the rocking behavior of the electrical cabinet system subjected to Reg. 1.60 and UHS. The high fidelity finite element (FE) model of the cabinet related to the shaking table test data was developed. In particular, the first two global modes of the cabinet from the experimental test were 16 Hz and 24 Hz, respectively. In addition, 30.05 Hz and 37.5 Hz were determined to be the first two local modes in the cabinet. The high fidelity FE model of the cabinet using the ABAQUS platform was extremely reconciled with shaking table tests. As a result, the dynamic properties of the cabinet were sensitive to electrical instruments, such as relays and switchboards, during the shaking table test. In addition, the amplification with respect to the vibration transfer function of the cabinet was observed on the third floor in the cabinet due to localized impact corresponding to the rocking phenomenon of the cabinet under Reg.1.60 and UHS. Overall, the rocking of the cabinet system can be caused by the low-frequency oscillations and higher peak horizontal acceleration. (c) 2021 Korean Nuclear Society, Published by Elsevier Korea LLC. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/).

키워드

CabinetSeismic qualificationHigh fidelityRocking behaviorRESPONSE SPECTRASTATE

식별자

Scopus EID
2-s2.0-85099862164
WoS UID
000663396800005
KCI
ART002726228