Optimal design of variable-path heat exchanger for energy efficiency improvement of air-source heat pump system

문서 유형
연구출판물 · 학술지 논문
등재
SCIEScopus
저널 순위
JCR Q1Scopus Q1
저널
APPLIED ENERGY290 · 2021
피인용
Web of Science 37Scopus 42
FWCI (Scopus)
1.71
JCR IF
JCR 2020 9.746
ISSN
0306-2619

저자

  1. 심재훈제1저자School of Mechanical Engineering, Pusan National University, Geumjeong-Gu, Busan 46241, Republic of Korea
  2. 이효인School of Mechanical Engineering, Pusan National University, Geumjeong-Gu, Busan 46241, Republic of Korea
  3. 정지환교신저자School of Mechanical Engineering, Pusan National University, Geumjeong-Gu, Busan 46241, Republic of Korea

초록

The optimal number of paths for the heat exchanger of an outdoor unit of a heat pump system depends on whether this heat exchanger functions as a condenser or an evaporator. A variable-path heat exchanger (VPHE) is proposed that can provide an optimal flow path for both condenser and evaporator conditions with one heat exchanger. The performance of VPHE was numerically analyzed, and the results showed that both the heat transfer capacity and pressure drop of the VPHEs increased. The performance of a VPHE with an upper and lower region ratio of 34:24 was enhanced by 22.1% in terms of heat transfer capacity per pumping power. Based on numerical simulation results, the potentially optimal refrigerant flow path was selected and VPHEs were manufactured to be incorporated into a heat pump system. The performance of the heat pump was experimentally measured under heating conditions, standard cooling conditions, part load cooling conditions, and overload cooling conditions. It was demonstrated that the COP of the heat pump employing VPHEs was increased by 15% under the standard rating condition and by 23% under part load cooling condition.

키워드

Heat pumpCondenserEvaporatorVariable-path heat exchangerPath optimization2-PHASE FLOW DISTRIBUTIONREFRIGERANT CIRCUITRYSIDE PERFORMANCEINDOOR AIRCONDENSERS