본문 바로가기

SOGI를 이용한 단상 계통연계형 인버터의 데드타임 보상

Dead time Compensation of Single-phase Grid-connected Inverter Using SOGI

문서 유형
연구출판물 · 학술지 논문
등재
KCI
저널
전력전자학회 논문지22(2) · pp.166 · 2017
피인용
KCI 0
ISSN
1229-2214

저자

  1. 성의석제1저자경남대학교
  2. 이재석경남대학교
  3. 황선환교신저자경남대학교
  4. 김장목부산대학교

초록

This study proposes a compensation method for the dead-time effects on a single-phase grid-connected inverter. Dead time should be considered in the pulse-width modulation gating signals to prevent the simultaneous conduction of switching devices, considering that a switching device has a finite switching time. Consequently, the output current of the grid-connected inverter contains odd-numbered harmonics because of the dead time and the nonlinear characteristics of the switching devices. The effects of dead time on output voltage and current are analyzed in this study. A new compensation algorithm based on second-order generalized integrator is also proposed to reduce the dead-time effect. Simulation and experimental results validate the effectiveness of the proposed compensation algorithm.

키워드

Single-phase grid-connected inverterDead timeSOGICurrent ripple reduction

식별자

KCI
ART002215840