제로에너지빌딩 구현을 위한 태양광열-지열 하이브리드 시스템의 성능분석
Performance Analysis of Hybrid System with PVT and GSHP for Zero Energy Building
- 문서 유형
- 연구출판물 · 학술지 논문
- 등재
- KCI
- 저널
- KIEAE Journal18(5) · pp.85 · 2018
- 피인용
- KCI 3
- ISSN
- 2288-968X
저자
초록
Purpose: Various renewable energy technologies such as photovoltaic, solar thermal and geothermal system are being utilized for zero energy building. However, technologies using a single heat source are highly affected by external conditions such as weather and changes in underground temperature. In this study, a hybrid system with PVT and GSHP was developed to overcome the disadvantage of individual system and to improve the reliability of energy production. In addition, this paper aims to analyze the performance of the system and calculate the energy independence rate according to the design capacity. Method: In this study, the dynamic energy simulation was conducted to quantitatively analyze building load and heat pump seasonal performance factor of heating and cooling of the hybrid system with PVT and GSHP. In addition, power production and power consumption were calculated according to the installation area of the PVT module. The building energy independence rate was calculated using the power production and power consumption results, and the zero energy building certification level was determined. Result: As the simulation result, heating peak load is 6.16kW, cooling peak load is 2.37kW and annual energy independence rate of Case 1 is 44.9%.
키워드
Zero energy buildingHybrid system with PVT and GSHPEnergy independence rate제로에너지빌딩태양광열-지열 하이브리드 시스템에너지 자립률
식별자
- KCI
- ART002400377



로그인