본문 바로가기

수치해석을 이용한 수직밀폐형 지열 시스템 영향인자의 민감도 분석- 난방운전을 중심으로

Sensitivity Analysis of the Design Factor for Vertical Closed-loop Geothermal System using Numerical Analysis - Focused on Heating Operation -

문서 유형
연구출판물 · 학술지 논문
등재
KCI
저널
KIEAE Journal18(5) · pp.55 · 2018
피인용
KCI 2
ISSN
2288-968X

저자

  1. 배상무제1저자부산대학교 건축공학과
  2. 김홍교부산대학교 건축공학과
  3. 전재영부산대학교
  4. 남유진교신저자부산대학교

초록

Purpose: Recently, in order to realize eco-friendly buildings, studies on renewable energy technologies have conducted in field of building energy. Among these technologies, a ground source heat pump (GSHP) system can achieve higher performance than conventional air source system. However, the GSHP system has been delayed due to high initial cost and lack of guidelines for performance analysis of various design factor. Therefore, this paper aims to proposed design and operation method to improve the performance of the GSHP system and to minimize the additional cost. Method: In this study, numerical simulation was conducted to accurately predict the heat exchanger rate (HER) and entering water temperature (EWT) of the GSHP system. The numerical simulation was coupled with soil model, ground heat exchanger (GHX) model and ground surface heat flux model. Furthermore, the performance of GSHP system was analyzed according to the operation method of the system such as flow rate, operation time, and limit temperature. Result: As a result, the HER and the EWT of base case were 34.3W/m, 10.26℃ respectively in the condition of 9.3lpm flow rate, 9 hours per day operation, and 5℃ limit temperature.

키워드

Ground Heat Pump (GSHP) SystemNumerical SimulationOperation MethodHeat Exchange Rate (HER)지열 히트펌프 시스템수치 시뮬레이션운전방법지중 채열량

식별자

KCI
ART002400372