Seismic performance of emergency diesel generator for high frequency motions
- 문서 유형
- 연구출판물 · 학술지 논문
- 등재
- KCISCIEScopus
- 저널 순위
- JCR Q1Scopus Q2
- 저널
- NUCLEAR ENGINEERING AND TECHNOLOGY51(5) · pp.1470 · 2019
- 피인용
- Web of Science 18Scopus 23KCI 4
- FWCI (Scopus)
- 1.06
- JCR IF
- JCR 2018 1.546
- ISSN
- 1738-5733
저자
- 정영수제1저자Seismic Research and Test Center, Pusan National University, 49 Busandaehak-ro, Yansan, Gyeongnam, 50612, Republic of Korea
- 백은림Seismic Research and Test Center, Pusan National University, 49 Busandaehak-ro, Yansan, Gyeongnam, 50612, Republic of Korea
- 전법규Seismic Research and Test Center, Pusan National University, 49 Busandaehak-ro, Yansan, Gyeongnam, 50612, Republic of Korea
- 장성진Seismic Research and Test Center, Pusan National University, 49 Busandaehak-ro, Yansan, Gyeongnam, 50612, Republic of Korea
- 박동욱교신저자Seismic Research and Test Center, Pusan National University, 49 Busandaehak-ro, Yansan, Gyeongnam, 50612, Republic of Korea
초록
The nuclear power plants in South Korea have been designed in accordance with the U.S. Regulatory Guide 1.60 (R.G 1.60) design spectrum of which the peak frequency range is 2-10 Hz. The characteristics of the earthquakes at the Korea nuclear power plant sites were observed to be closer to that of Central and Eastern United States (CEUS) than the R.G 1.60, which is a lower amplification in a low frequency range, and a higher amplification in a high frequency range. The possibility of failure for sensitive power plant components in the high frequency range has been considered and evaluated. In this study, in order to improve the reliability of nuclear plant and administrative control procedures, seismic tests of an emergency diesel generator (EDG) were conducted using a shaking table under both high and low frequency ranges. From the tests, oil/lubricant leaks from the bolt connections, the fuel filter and the fuel inlet were observed. Therefore, the check list of nuclear plant components after an earthquake should include bolt connections of EDG as well as anchor bolts. (C) 2019 Korean Nuclear Society, Published by Elsevier Korea LLC.
키워드
Emergency diesel generatorSeismic performanceHigh frequency motionShaking table test