Experimental study of R134a/R410A cascade cycle for variable refrigerant flow heat pump systems
- 문서 유형
- 연구출판물 · 학술지 논문
- 등재
- KCISCIEScopus
- 저널 순위
- JCR Q3Scopus Q2
- 저널
- JOURNAL OF MECHANICAL SCIENCE AND TECHNOLOGY29(12) · pp.5447 · 2015
- 피인용
- Web of Science 15KCI 4
- JCR IF
- JCR 2014 0.838
- ISSN
- 1738-494X
저자
초록
Cascade cycle is widely applied to heat pumps operating at low ambient temperature to overcome problems such as low heating capacity and Coefficient of performance (COP) deterioration A number of researches have been conducted on cascade cycle heat pumps, but most of those studies were focused on system optimization to determine optimal intermediate temperature in air-to-water heat pumps. However, experimental optimization in regard to air and water heating simultaneously using a cascade cycle has been an understudied area. Therefore, we focused on experimental analysis for a cascade system with Variable refrigerant flow (VRF) heat pumps. Experiments were conducted under a variety of operating conditions, such as ambient and water inlet temperature. COP increased up to 16% when water inlet temperature decreased. COP of VRF heat pumps with cascade cycle is three-times higher compared with conventional boilers as well as 17% higher compared to single heat pumps.
키워드
Cascade cycleHeat pumpIntermediate temperatureR134aR410AVariable refrigerant flowTHERMODYNAMIC ANALYSISCOOLING APPLICATIONSOPTIMIZATIONVERIFICATIONTEMPERATURES