Experimental study of R134a/R410A cascade cycle for variable refrigerant flow heat pump systems

문서 유형
연구출판물 · 학술지 논문
등재
KCISCIEScopus
저널 순위
JCR Q3Scopus Q2
저널
JOURNAL OF MECHANICAL SCIENCE AND TECHNOLOGY29(12) · pp.5447 · 2015
피인용
Web of Science 15KCI 4
JCR IF
JCR 2014 0.838
ISSN
1738-494X

저자

  1. 김정훈제1저자부산대학교
  2. 이재완부산대학교
  3. 최환종LG전자
  4. 이상훈LG전자
  5. 오새기LG전자
  6. 박원규교신저자부산대학교

초록

Cascade cycle is widely applied to heat pumps operating at low ambient temperature to overcome problems such as low heating capacity and Coefficient of performance (COP) deterioration A number of researches have been conducted on cascade cycle heat pumps, but most of those studies were focused on system optimization to determine optimal intermediate temperature in air-to-water heat pumps. However, experimental optimization in regard to air and water heating simultaneously using a cascade cycle has been an understudied area. Therefore, we focused on experimental analysis for a cascade system with Variable refrigerant flow (VRF) heat pumps. Experiments were conducted under a variety of operating conditions, such as ambient and water inlet temperature. COP increased up to 16% when water inlet temperature decreased. COP of VRF heat pumps with cascade cycle is three-times higher compared with conventional boilers as well as 17% higher compared to single heat pumps.

키워드

Cascade cycleHeat pumpIntermediate temperatureR134aR410AVariable refrigerant flowTHERMODYNAMIC ANALYSISCOOLING APPLICATIONSOPTIMIZATIONVERIFICATIONTEMPERATURES