Heat pump control method based on direct measurement of evaporation pressure to improve energy efficiency and indoor air temperature stability at a low cooling load condition

문서 유형
연구출판물 · 학술지 논문
등재
SCIEScopus
저널 순위
JCR Q1Scopus Q1
저널
APPLIED ENERGY132 · pp.99 · 2014
피인용
Web of Science 28
JCR IF
JCR 2013 5.261
ISSN
0306-2619

저자

  1. 박영성제1저자School of Mechanical Engineering, Pusan National University, South Korea
  2. 정지환교신저자School of Mechanical Engineering, Pusan National University, South Korea
  3. Ahn, Byoung HaAir Conditioning and Energy Lab, LG Electronics, South Korea

초록

The control systems of conventional heat pumps have an input of refrigerant temperature at the evaporator outlet to maintain superheat at proper level. In order to develop a control method that can be used to achieve better indoor thermal comfort and energy efficiency at a low cooling load condition than the current control method, a new method of the evaporation pressure control based on the evaporator outlet pressure reading (EPCP) was developed. The changes in the stability of indoor air temperature and power consumption were measured while changing the compressor frequency in accordance with the new control method. Compared with the evaporation pressure control based on the evaporator outlet temperature reading, the EPCP control method appeared to improve the stability of room air temperature or occupant thermal comfort significantly. (C) 2014 Elsevier Ltd. All rights reserved.

키워드

Heat pumpIndoor air temperatureControlCooling modeEvaporation pressurePERFORMANCE