본문 바로가기

Analysis and Compensation of Current Measurement Errors in a Doubly Fed Induction Generator

문서 유형
연구출판물 · 학술지 논문
등재
KCISCIEScopus
저널 순위
JCR Q4Scopus Q3
피인용
Web of Science 3KCI 3
JCR IF
JCR 2013 0.517
ISSN
1975-0102

저자

  1. 손영득Pusan National University
  2. 김장목교신저자부산대학교
  3. 임원상부산대학교
  4. Han-Seok ParkPusan National University

초록

It is necessary to measure the current of rotor for controlling the active and reactive power generated by the stator side of the doubly fed induction generator (DFIG) system. There are offset and scaling errors in the current measurement. The offset and scaling errors cause one and two times current ripples of slip frequency in the synchronous reference frame of vector control, respectively. This paper proposes a compensation method to reduce their ripples. The stator current is variable according to the wind force but the rotor current is almost constant. Therefore input of the rotor current is more useful for a compensation method. The proposed method adopts the synchronous d-axis current of the rotor as the input signal for compensation. The ripples of the measurement errors can be calculated by integrating the synchronous d-axis stator current. The calculated errors are added to the reference current of rotor as input of the current regulator, then the ripples are reduced. Experimental results show the effectiveness of the proposed method.

키워드

DFIGRipple errorsCurrent sensor errorOffsetScalingSynchronous d-axis rotor currentAC MOTOR-DRIVESWIND TURBINESPOWER-SYSTEM

식별자

WoS UID
000332352500018
KCI
ART001854952