The selection of volume ratio of two-stage rotary compressor and its effects on air-to-water heat pump with flash tank cycle
- 문서 유형
- 연구출판물 · 학술지 논문
- 등재
- SCIEScopus
- 저널 순위
- JCR Q1Scopus Q1
- 저널
- APPLIED ENERGY104 · pp.187 · 2013
- 피인용
- Web of Science 65
- JCR IF
- JCR 2012 4.781
- ISSN
- 0306-2619
저자
- Ko, Younghwan제1저자Air Conditioning and Energy Lab., LG Electronics, South Korea
- Park, SangkyoungAir Conditioning and Energy Lab., LG Electronics, South Korea
- Jin, SimonAir Conditioning and Energy Lab., LG Electronics, South Korea
- Kim, ByungsoonAir Conditioning and Energy Lab., LG Electronics, South Korea
- 정지환교신저자School of Mechanical Engineering, Pusan National University, South Korea
초록
A conventional heat pump exhibits performance degradation even though larger heating capacity is needed as the outdoor temperature declines. As a way to prevent the performance degradation, a heat pump with an inverter-driven two-stage rotary compressor and vapor injection (VI) cycle was investigated for an air-to-water heat pump (AWHP) system employing a flash tank. The volume ratio of two cylinder of a two-stage rotary compressor has significant effect on the performance of the AWHP so that it was experimentally investigated. Based on this result, a two-stage rotary compressor designed with an optimized volume ratio was manufactured and incorporated into the AWHP system. It was found that the VI AWHP system improved the heating capacity by 48% and the COP by 36% compared to those values for the conventional AWHP at water temperature of 60 degrees C and ambient temperature of -15 degrees C. This VI AWHP system can be used for cold climate applications. (C) 2012 Elsevier Ltd. All rights reserved.
키워드
Two-stage rotary compressorVolume ratioVapor injectionAir-to-water heat pumpFlash tankREFRIGERANT INJECTIONSCROLL COMPRESSORCOLD REGIONSPERFORMANCE