A Capacitance Estimation of Film Capacitors in an LCL-Filter of Grid-Connected PWM Converters
- 문서 유형
- 연구출판물 · 학술지 논문
- 등재
- KCISCIEScopus
- 저널 순위
- JCR Q3Scopus Q2
- 저널
- JOURNAL OF POWER ELECTRONICS13(1) · pp.94 · 2012
- 피인용
- Web of Science 10KCI 0
- JCR IF
- JCR 2011 0.842
- ISSN
- 1598-2092
저자
초록
A capacitor deterioration of LCL-filter grid-connected PWM converters is progressed by the self-healing mechanism. It leads to the degradation of the filter performance and drop of power factor. Thus, it is required to diagnose fault-point of capacitors and determine the replacement time. Typically, the fault of capacitors is determined when the capacitance is reduced up to 80% from initial value. This paper proposes algorithm to the determine capacitor replacement time of an LCL filter. The algorithm takes the advantage of change of the response on the injected resonant frequency corresponding to 80% value from the initial capacitance. The results of the algorithm are demonstrated through simulations and experiments.
키워드
Deterioration of film capacitorGrid connected PWM converterInjection of resonant frequencyLCL filter3-PHASE ACTIVE RECTIFIERVOLTAGE-SOURCE CONVERTERPOWER FILTERSDESIGNCONTROLLERINVERTERSYSTEM
식별자
- WoS UID
- 000313763600011
- KCI
- ART001737337



로그인
연구물 목록으로