Performance evaluation under the actual operating condition of a vertical ground source heat pump system in a school building

문서 유형
연구출판물 · 학술지 논문
등재
SCIEScopus
저널 순위
JCR Q1Scopus Q1
저널
ENERGY AND BUILDINGS50 · pp.1 · 2012
피인용
Web of Science 36
JCR IF
JCR 2011 2.386
ISSN
0378-7788

저자

  1. 김의영제1저자School of Mechanical Engineering, Pusan National University, South Korea
  2. 이재근School of Mechanical Engineering, Pusan National University, South Korea
  3. 정영만School of Mechanical Engineering, Pusan National University, South Korea
  4. 황유진교신저자School of Mechanical Engineering, Pusan National University, South Korea
  5. Lee, SangheonLG Electronics, South Korea
  6. Park, NaehyunLG Electronics, South Korea

초록

This study is to evaluate the performance of a ground source heat pump (GSHP) system installed in the Pusan National University, Korea. The GSHP system consists of ground heat exchanger (GHE), measuring devices and heat pumps which have 2 compressors (inverter type and fixed type). The closed vertical type GHE is constructed with 24 boreholes of 175m in depth. The outdoor temperature, the indoor temperature and relative humidity, the inlet and outlet temperature of circulating water are obtained. Also, the electricity consumption of compressor and cooling (heating) load are measured in order to analyze the COP of heat pump. From the measuring data, the variation of ground temperature at 2.5 m, 5.0 m in depth are affected by outdoor air temperature. But it is proved that the ground temperature is almost constant below 10 m in depth. In cooling period, the COP of the heat pump is 6.0-10.9 at partial load condition, while the overall system COP is 4.3-7.4. In heating period, the COP of the heat pump is 4.3-8.3 at partial load condition, while the overall system COP is 3.0-6.2. (c) 2012 Elsevier B.V. All rights reserved.

키워드

Ground source heat pumpCooling performanceHeating performanceGround heat exchangerAIR-SOURCEDESIGN