본문 바로가기

An experimental study on oil discharge ratio at inverter-driven high shell pressure scroll compressor using R410A/PVE

문서 유형
연구출판물 · 학술지 논문
등재
SCIEScopus
저널 순위
JCR Q1
저널
INTERNATIONAL JOURNAL OF REFRIGERATION34(1) · pp.105 · 2011
피인용
Web of Science 17
JCR IF
JCR 2010 1.439
ISSN
0140-7007

저자

  1. Yoon, Pilhyun제1저자LG, Air Conditioning Lab, KO
  2. Kang, DonghoonLG, Air Conditioning Lab, KO
  3. Kim, CholhwanLG, Air Conditioning Lab, KO
  4. Ahn, SungyongLG, Air Conditioning Lab, KO
  5. Chung, BaikyoungLG, Air Conditioning Lab, KO
  6. Kim, ByungsoonLG, Air Conditioning Lab, KO
  7. 이재근부산대학교, 공과대학, 기계공학부, KO
  8. 황유진교신저자부산대학교, 공과대학, 기계공학부, KO

초록

In this study, the oil discharge characteristics of a high shell pressure scroll compressor, which uses R410A as the refrigerant and PVE as the oil, were measured according to the conditions for oil management. The measurement of oil discharge ratio (ODR) in the system is very important to secure the operational reliability. It was made in real time through the refractive index sensor. ODR was greatly influenced by the mass flow rate and the dynamic viscosity of the refrigerant. As the rotation frequency of the compressor became higher, ODR increased rapidly. ODR at 120 Hz was 4.22 times higher than that at 60 Hz. At the same rotation frequency of the compressor, the increase of the suction pressure also played a role in increasing the ODR. In addition, in the zone where the ODR increased rapidly, the compressing efficiency of the compressor decreased significantly. (C) 2010 Elsevier Ltd and IIR. All rights reserved.

키워드

Scroll compressorR410AOilDischargeMIXTURECIRCULATION

식별자

WoS UID
000286343500011