Skip to content

Seismic behavior of electrical cabinets with cast-in-place anchors: influence of concrete cracks and multi-bay installation

Document Type
Publications · Journal Article
Registered DB
KCISCIEScopus
Journal Ranking
JCR Q1Scopus Q1KCI Q3
Citation
Web of Science 1Scopus 1KCI 0
FWCI (Scopus)
0
JCR IF
JCR 2024 2.6
ISSN
1738-5733

Authors

  1. Jeon, Bub-GyuFirst authorPusan Natl Univ, Seism Res & Test Ctr, 49 Busandaehak Ro, Yangsan 50612, Gyeongnam, South Korea
  2. Kim, Sung-WanCorresponding authorPusan Natl Univ, Seism Res & Test Ctr, 49 Busandaehak Ro, Yangsan 50612, Gyeongnam, South Korea
  3. Park, Dong-UkPusan Natl Univ, Seism Res & Test Ctr, 49 Busandaehak Ro, Yangsan 50612, Gyeongnam, South Korea
  4. Lee, Chae-BeenPusan Natl Univ, Seism Res & Test Ctr, 49 Busandaehak Ro, Yangsan 50612, Gyeongnam, South Korea
  5. Hahm, DaeGiKorea Atom Energy Res Inst, Struct & Seism Safety Res Div, 111 Daedeok Daero 989 beon Gil, Daejon 34057, South Korea
  6. Lee, Hong-PyoCorresponding authorKorea Hydro & Nucl Power Co LTD, Cent Res Inst, 70 Yuseong Daero 1312 Beon Gil, Daejeon 34101, South Korea

Abstract

Electrical cabinets are typically assembled in a multi-bay configuration, connecting two or more modules, and the structural implications of this setup must be carefully addressed. Concrete foundation cracks, often observed during field investigations at power plants, represent a common form of support deterioration. This study fabricated concrete foundations to simulate intact conditions and cracked conditions with 0.5 mm and 1.0 mm wide cracks at anchor locations. A simplified electrical cabinet model was constructed in single-bay, two-bay, and three-bay configurations and anchored to the concrete foundations using cast-in-place anchors to consider the effects of multi-bay configuration and support deterioration. Three-axis shaking table tests were conducted, including resonant frequency search and seismic fragility tests. The results indicated that cracks at the anchor locations can increase the uncertainty in the cabinet's resonant frequency. Specifically, when the concrete foundation was intact, seismic performance improved as the number of connected bays increased. However, cracks up to 1.0 mm in width degraded the seismic performance of multi-bay configurations but had a negligible impact on the single-bay cabinet. Moreover, distinct damage modes were observed between single-bay and multi-bay conditions.

Keywords

AnchorElectrical cabinetNuclear power plantSeismic fragilitySeismic performanceShaking table test

Identifiers

Scopus EID
2-s2.0-105029421105
WoS UID
001677213300001
KCI