Skip to content

An Experimental Study on the Dynamic Behavior of the Seismic Isolator for Telecommunication Equipment Installed in a 15-Story Reinforced Concrete Building

15층 철근콘크리트 건물에 설치된 통신설비 면진장치 동적거동에 대한 실험적 연구

Document Type
Publications · Journal Article
Registered DB
KCI
Journal Ranking
KCI Q2
Journal
한국지진공학회논문집 (EESK)25(6) · pp.241 · 2021
Citation
KCI 0
ISSN
1226-525X

Authors

  1. Choi, HyoungsukFirst author부산대학교
  2. Jung, Donghyuk부산대학교
  3. Seo, Young-Deuk부산대학교 지진방재연구센터
  4. Baek, Eun-Rim부산대학교

Abstract

Communication facilities play an essential role in disaster situations. Therefore, communication facilities need to have structural and functional safety during and after earthquakes. Recently, technology for partial seismic isolation has been increasing to protect data facilities and communication equipment installed in buildings from earthquakes. However, excessive displacement may occur in the seismic isolator during an earthquake due to the resonance between the building and the seismic isolator having long-period characteristics, which may cause overturning and separation of the installed equipment. In this study, analytical and experimental studies were conducted to evaluate the safety of seismic isolators installed in high-rise buildings. It was confirmed that damages might occur in buildings' seismic isolator, with resonance characteristics of less than 1 Hz.

Keywords

Tele-communication equipmentSeismic isolatorLong periodConcrete buildingResonance

Identifiers

KCI
ART002770568