Skip to content

A study on the optimal arrangement of tube bundle for the performance enhancement of a steam turbine surface condenser

Document Type
Publications · Journal Article
Registered DB
SCIEScopus
Journal Ranking
JCR Q1Scopus Q1
Journal
APPLIED THERMAL ENGINEERING166 · 2020
Citation
Web of Science 16Scopus 19
FWCI (Scopus)
0
JCR IF
JCR 2019 4.725
ISSN
1359-4311

Authors

  1. Park, Yong GapFirst authorRolls-Royce and Pusan National University Technology Centre in Thermal Management, Pusan National University, Busan 46241, Republic of Korea
  2. Yoon, Sang YoulRolls-Royce and Pusan National University Technology Centre in Thermal Management, Pusan National University, Busan 46241, Republic of Korea
  3. Seo, Young MinCorresponding authorRolls-Royce and Pusan National University Technology Centre in Thermal Management, Pusan National University, Busan 46241, Republic of Korea
  4. Ha, Man YeongSchool of Mechanical Engineering, Pusan National University, Busan 46241, Republic of Korea
  5. Park, Young MinTechnology Development Part II R&D Center, Donghwa Entec, Busan 46753, Republic of Korea
  6. Koo, Byoung SooTechnology Development Part II R&D Center, Donghwa Entec, Busan 46753, Republic of Korea

Abstract

A porous medium model was used for numerical and experimental investigations of a system that includes a tube bundle inside a steam turbine surface condenser. A condensation model was developed to predict the condenser performance using user-defined functions (UDFs) in the commercial computational fluid dynamics software FLUENT. The shell-side pressure drop around the tube bundle is an important indicator for the condenser performance and can be used to compare different condenser-tube arrangements. The condenser performance was analyzed using various numerical results, such as the absolute pressure, condensation mass flow rate, velocity magnitude, and air mass fraction. Detailed effects of the various parameters of tube bundle are discussed. These parameters had a great influence on the condenser performance. The numerical data were generally in good agreement with those obtained by experiments. An important practical finding from this study is that changing tube bundle can significantly improve the condenser performance by reducing the shell-side pressure drop. Consequently, the optimized model has approximately 40% better pressure drop performance than the base model, and the numerical results were verified with the experiments established by Donghwa Entec.

Keywords

Steam surface condenserTube arrangementPorous mediaThermal resistance networkCondensationHEAT-TRANSFER2-PHASE FLOWNUMERICAL-MODELSYSTEMSIMULATIONPREDICTIONEJECTORPUMPAIR

Identifiers

Scopus EID
2-s2.0-85075853841
WoS UID
000512220900070