Skip to content

Heating Performance Analysis of Open-loop Geothermal System Applying Pairing Technology Based on Verification Experiment

실증실험에 근거한 관정간 페어링 적용 개방형 지열 시스템의 난방성능 분석

Document Type
Publications · Journal Article
Registered DB
KCI
Journal
KIEAE Journal18(2) · pp.25 · 2018
Citation
KCI 1
ISSN
2288-968X

Authors

  1. Kim, HongkyoFirst author부산대학교 건축공학과
  2. Bae, Sang Mu부산대학교 건축공학과
  3. 이병호한국지하수지열협회
  4. Nam, YujinCorresponding author부산대학교

Abstract

Purpose: Open-loop geothermal systems can be expected to have higher performance than a closed-loop geothermal systems. However, performance of open-loop geothermal systems are significantly affected by hydrogeological conditions such as porosity, permeability and groundwater temperature. In addition, clogging occurs due to floating particle in the well in case of long-term operation. Therefore, it is necessary to develop technology that ensure stable system performance and preserve hydrogeological conditions in the ground. Method: In this study, pairing technology between diffusion well and supply well was developed in order to maintain stable system performance and minimize the influence on the underground environment. In this paper, underground water level and temperature were calculated according to operation of system with the pairing technology. Performance of the system was compared to that of standing column well(SCW) geothermal system. Result: During heating operation of the system, groundwater level increased to depth of the pairing (- 1.5 m), but operation was not stopped. Finally, S.COP of two-well pairing system and SCW geothermal system was 2.71, 2.79 respectively.

Keywords

개방형 지열 시스템페어링 기술지하수위Open-loop geothermal systemParing technologyGroundwater level

Identifiers

KCI
ART002342252